Initialization Program Writing of Mitsubishi PLC Module FX3U-4AD

Nov 12, 2021

The initialization program of Mitsubishi PLC analog input module FX3U-4AD (FX3U-4AD initialization program, FX3U-4AD programming).

When initializing FX3U-4AD, please execute the following procedure.

The input mode (BFM #0), offset data (BFM #41~#44) and gain data (BFM #51~#54) are returned to the factory state.

1. Conditions

An example of a sequence program that operates under the following conditions is described.

1) System configuration

FX3U-4AD (unit number: 0) is connected to the FX3U programmable controller.

2) Assignment of soft elements: X000 is the initialization command of FX3U-4AD.

2. Examples of sequence control procedures

· For FX3U, FX3UC programmable controller

· For FX3G, FX3GC, FX3U, FX3UC programmable controller

3. Attention

· It takes about 5 seconds from the beginning to the end of the initial execution.

Do not perform setting (writing) to the buffer memory area.

· After initialization, the value of BFM #20 becomes K0.

· The setting of setting value change prohibition (BFM #19) has priority. When performing initialization, please set BFM #19 to K2080.

FX3U-4AD initialization program, FX3U-4AD programming